Startup
9000X AF Drives MN04001004E—May 2011 www.eaton.com 55
Closed Loop Vector Control Manual Tuning (SPX9000 Only)
For some non-standard motors, the auto-tune is not
sufficient. Closed loop control mode is used when enhanced
performance near zero speed and better steady starts and
dynamic speed accuracy at higher speeds are needed.
Tuning Steps
Set the motor nameplate values.
Nominal voltage of motor P1.1.6
Nominal frequency of motor P1.1.7
Nominal speed of motor P1.1.8
Nominal current of motor P1.1.9
Motor Power Factor (Cos Phi) P1.1.10
Check encoder pulse/revolution rate and set this value to
expander menu P6.3.1.1. Parameter is only visible if OPTA4
or OPTA5 is installed to slot C.
Set motor control mode to open loop frequency control
(P1.6.1 = 0).
Run the motor unloaded at 2/3 rated speed using a frequency
reference. Read the motor current from the monitoring menu
(V1.4) or use 9000X drive for monitoring. This current is the
motor magnetizing current. This value should match a
nameplate magnetizing current value if given.
Set the motor magnetizing current P1.6.17.1.
Check the expander board menu (monitoring page V6.3.2.1),
to be sure that the encoder frequency is approximately the
same as the output frequency, and that the direction is
correct. If the encoder frequency direction is opposite the
output frequency (negative value), change the motor phase
order to encoder connection. The expander board menu also
has a parameter to invert the signal if rewiring is not an
option.
Set motor control mode to closed loop (P1.6.1 = 3 or 4).
Fine Tuning
Tune parameter P1.6.17.6 (slip adjust) to get the motor
voltage slightly above the linear V/f curve when motor is
loaded and slightly below when motor is generating.
Using the linear V/f curve (P1.6.3 = 0), run the motor in
frequency control mode (P1.6.1 = 0) at about 2/3 of the
motor nominal frequency and check motor voltage (V7.7).
At 40 Hz, voltage should be 40/60*460V = 307V.
Run the motor in closed loop control mode with same
reference and check the motor voltage. Adjust P1.6.17.6
(slip adjust) so that motor voltage is slightly above the linear
V/f curve. If motor voltage is low, decrease the value of slip
adjust (P1.6.17.6).
Closed Loop Motor Voltage
40 Hz
60 Hz
460V
307
V
Closed Loop
Motor Voltage
Przeglądanie stron 64