Startup
9000X AF Drives MN04001004E—May 2011 www.eaton.com 51
V/f Curve Manual Tuning
When tuning the V/f curve manually (not using
identification run) the motor shaft must be unloaded and
the motor control mode set to frequency control (P1.6.1).
The following parameters are adjusted to tune the V/f curve:
Parameters
V/f ratio selection P1.6.3
Field weakening point P1.6.4
Voltage at field weakening point P1.6.5
V/f curve midpoint frequency P1.6.6
V/f curve midpoint voltage P1.6.7
Output voltage at zero frequency P1.6.8
When using a linear V/f curve with increased zero
frequency voltage, ensure that the motor current does
not increase too much between 3–7 Hz.
Tuning Steps
Set the motor nameplate values.
Nominal voltage of motor P1.1.6
Nominal frequency of motor P1.1.7
Nominal speed of motor P1.1.8
Nominal current of motor P1.1.9
Motor Power Factor (Cos Phi) P1.1.10
Run the motor unloaded at 2/3 rated speed using a frequency
reference. Read the motor current from the monitoring menu
(V7.4) or use 9000X drive for monitoring. This current is the
motor magnetizing current. This value should match a
nameplate magnetizing current value if given.
If the motor will only be run in closed loop, skip to section on
closed loop vector control tuning.
Change the V/f curve ratio selection to
programmable-mode = 2 (P1.6.3).
Run motor with zero frequency reference and increase motor
zero point voltage (P1.6.8) until motor current is
approximately the same as the motor magnetizing current.
(If motor is only in the low frequency area for short periods, it
is possible to use up to 80% of rated current.)
Then, set the midpoint voltage (P1.6.7) to 1.4142
*P1.6.8 ( * Zero Point Voltage) and midpoint
frequency (P1.6.6) to value P1.6.8/100%*P1.1.7.
([ZeroPoint Voltage/100%]*Nominal frequency of motor.)
2
P1.6.72 * P1.6.8
P1.6.8
100
----------------
* P1.1.7
=
=
P1.6.6